Dongguan Habotest Instrument Technology Co.,Ltd
Place of Origin: | China |
Brand Name: | HABOTEST |
Certification: | CE,ROHS,EMC etc. |
Model Number: | HT5910 |
Minimum Order Quantity: | Negotiable |
---|---|
Price: | Negotiable |
Packaging Details: | Manual, Accessaries, Individual gift box, 20pcs /cartoon |
Payment Terms: | T/T, Western Union |
Supply Ability: | 5000pcs/month |
Features: | Loop Resistance; Frequency; Contact Voltage; Tripping Current Etc. | Color: | Digital Earth Resistance Tester |
---|---|---|---|
Material: | ABS+PC | Size: | 180*140*65mm |
Weight: | 950g | Power: | 6*LR14 Batterries |
High Light: | digital resistance meter |
HT5910 Digital Resistance Meter RCD Loop Tester Multimeter for GFCI Loop Resistance Testing
1. Comply with IEC/EN 61010-1 1000V CAT II,600V CAT III Safety standards
2. Maximum common mode voltage:600V AC RMS
3. Display method:it is displayed on the LCD with maximum value at 6000
4. Measuring range selection:Auto/manual measuring range
5. Frequency detection:Auto
6. Overrange indication:”>”
7. Power consumption:100mW
8. Storage temperature:-20~70C
9. Working temperature:0~40C
10. Temperature factor:When the temperature is lower than 18C or above 28C the factor is per(°) x 0.05 x (appointed accuracy)
11. Electromagnetic compatibility:in a 3V/M RF (Radio Frequency) magnetic field,accuracy = appointed accuracy;otherwise,the accuracy is not appointed.
12. Storage elevation:12000m
13. Usage elevation:2000m CAT III 600V;3000 CAT II 600V
14. Size:200*155*76mm
15. Net Weight:about 500g
Trip-out time | x1 IΔΝ300(slow 500ms) | ±3ms | 0.1ms | |
x5 IΔΝ40ms(slow 150ms) | ||||
Trip-out current | (0.2~1.1)IΔΝ | ±0.1 IΔΝ | 0.05 IΔΝ | |
Contact voltage | 0~99.9V | ±(10%+0.2V) | 0.01,0.1V | |
Alternating Voltage | 0~440V | ±(3%+3V) | 1V | |
(UI-N,UL-L,UL-E) | ||||
Frequency | DC,45~65Hz | ±1Hz | 1Hz | |
Loop Resistance | 0~19.9V | ±(10%+0.2V) | 0.01V | |
(RL) | 10.0~99.9V | 0.1V | ||
RL Current Test | 0.5IΔΝ | ±(10%+10d) | 0.05IΔΝ | |
Multiplying Power | x0.5,x1,x5 | |||
of test Current | ||||
Current Level (IΔΝ) | 10mA,30mA,100mA | |||
300mA,500mA | ||||
Trigger Phase Angle | 0°or 180° | |||
RCD Test Current Selection Table | ||||
IΔΝ(mA) | IΔX1/2 (mA) | IΔX1(mA) | IΔX5(mA) | Auto(mA) |
10 | 5 | 10 | 50 | 10 |
30 | 15 | 30 | 150 | 30 |
100 | 50 | 100 | 500 | 100 |
300 | 150 | 300 | 1500 | 300 |
500 | 250 | 500 | ------- |
500 |
Pocket Size Auto Range Digital Multimeter , 4000 Count Multimeter For Electrician
Pocket Size Auto Electrical Digital Multimeter , AC DC 600V NCV 4000 Count Multimeter
Handheld Digital Multimeter Smart TRMS 6000 Count NCV LIve Wire Frequency
HT200D AC DC Clamp Meter , Mini Clamp Meter With Resistance Data Max Hold / Continuity
Portable Digital Clamp Meter , TRMS Clamp Meter Current Voltage Resistance Capacitance
HT206A Digital Clamp Meter AC Current Voltage Resistance Continuity Measuring Tester
RCD GFCI Socket Outlet Tester With Voltage Measurement OEM Available
Black Plug Socket Tester 62*65.5*56 Mm Dimensions With Voltage Measurement
HT106 Check Plug Socket Tester 110~230VAC Voltage Range Dimension 62*65.5*56 mm
| Sitemap